Bulletin 700-HXM
Timing Relays
179
Operating Mode, Continued
Input/Output Mode Settings
Counter Function
If there is a power failure during output ON, output will turn ON again when the power supply has recovered. For
one-shot output, an output will be made again for the duration of the output time setting once the power supply has
resumed.
Output timing restarted during one-shot outputs is ignored.
Note:
t-a:Less than the output time
t:Output time
Totalizing Counter Operation
Input Mode
Up Down Up/Down B.C
Output
mode
N
F
C
K
Totalizing counter continues to count the present value, regardless of whether
an reset input (by the reset key) has been made to reset the PV.
When totalizing count value is reset, the PV is reset at the same time.
The totalizing count range is 0…99,999,999. If the totalizing count exceeds
99,999,999, the count returns to 0. If the count drops below 0, it becomes
99,999,999.
Reset
9999
0
-999
Output
SV
Reset
9999
0
-999
Output
SV
Reset
9999
0
-999
Output
SV
tt t
ttt-a
ttt-a
Reset
9999
0
-999
Output
SV
t-a t t-a
t-a t
t-a t
Reset
Totalizing
count reset
(reset key)
PV
Totalizing
count value
page 18m