Two breaker alarm indicators (red LED) are provided on the front side of the panel. A separate
breaker alarm indicator is provided for each of the two power output buses (A and B). The
breaker alarm indicator turns on if any circuit breaker on the corresponding power bus trips.
The breaker alarm indicator turns off when the tripped breaker is placed in the on position. The
breaker alarm indicators cannot be field-replaced.
1.15 Cooling
The Select Series circuit breaker panel relies on convection air flow for cooling. Holes are
provided on the top and bottom of the panel to allow heated air to escape from the panel and
cool air to enter. At least one rack unit of space must be provided above and below the panel to
allow for air circulation.
1.16 Specifications
The specifications for the Select Series circuit breaker panel are listed in Table 2.
Table 2. Circuit Breaker Panel Specifications
PARAMETER SPECIFICATION REMARKS
Physical
Weight 10 lbs. (4.54 kg)
Dimensions (HxWxD) 1.73 x 17.13 x 11.11 inches
(43.9 x 435 x 282 mm)
See Figure 3
Color Putty white
Rack mounting 19- or 23-inch EIA or WECO hole spacing
Electrical
Operating voltages –24 Vdc
–48 Vdc
–21 to –30 Vdc tolerance
–42 to –56 Vdc tolerance
Input current 100 Amps per bus maximum
Breaker type Magnetic actuation, manual
reset, replaceable
1- pole or 2-pole
Breaker mounting positions Eight 1-pole per bus (16 total) or
Four 2-pole per bus (8 total
Or any combination of 1- and 2-
pole breakers
Maximum breaker size 50 Amps
Input terminal type 2-hole compression lug 0.625 inch between centers
Output terminal type Screw down terminal (8-32) Max lug width 0.378 inches
Alarm terminal type Screw down terminal (3-48) Max lug width 0.20 inches
Alarm contact voltage 110 Vac, 125 Vdc maximum
Alarm contact current 1 Amp maximum
Grounding connections Two #10 studs #10 ring terminals