The cursor, flashing part of display, is shown below in bold type.
Change measuring range of current output and value for error messages (Fct. 1.05):
Change measuring range from 04-20 mA to 00-20 mA
Change value for error messages from 0 mA to 22 mA
Key Display Description
If ”YES“ set under Fct. 3.04 ENTRY CODE, key in the
9-keystroke CODE 1 now: → → → ↑ ↑ ↑ ↵ ↵ ↵
Fct. 1.00 OPERATION
Fct. 1.01 FULL SCALE
4x Fct. 1.05 CURRENT I
FUNCT. I
→↵ RANGE I If ”REV. RANGE“ appears here,
press keys and again.
04-20 mA Old current range
2x 00-20 mA New current range
I ERROR
0 mA Old value for error messages
22 mA New value for error messages
Fct. 1.05 CURRENT I
Fct. 1.00 OPERATION
STORE YES
- - - - - - - - - - - - / - - - Measuring range with new data for the current output
Examples of setting the signal converter 4.7