4/12
The cursor, flashing part of display, is shown below in bold type.
• Change measuring range of current output and value for error messages (Fct. 1.05):
• Change measuring range from 04-20 mA to 00-20 mA
• Change value for error messages from 0 mA to 22 mA
Key Display Description
→ If ”YES“ set under Fct. 3.04 ENTRY CODE, key in the
9-keystroke CODE 1 now: → → → ↑ ↑ ↑ ↵ ↵ ↵
Fct. 1.00 OPERATION
→ Fct. 1.01 FULL SCALE
4x ↑ Fct. 1.05 CURRENT I
→ FUNCT. I
→↵ RANGE I If ”REV. RANGE“ appears here,
press keys → and ↵ again.
→ 04-20 mA Old current range
2x ↑ 00-20 mA New current range
↵ I ERROR
→ 0 mA Old value for error messages
↑ 22 mA New value for error messages
↵ Fct. 1.05 CURRENT I
↵ Fct. 1.00 OPERATION
↵ STORE YES
↵ - - - - - - - - - - - - / - - - Measuring range with new data for the current output
Examples of setting the signal converter 4.7
Comentários a estes Manuais