voltage between the two test points labeled CURRENT or VOLTAGE. The voltage should be 0.6 VDC +/- 0.03 volts to
equal 60ma.
NOTE:
Current measurement test is not required when the span is fiber out to the customer site and the smartjack is
located in the same bay or adjacent bay as the mux and is locally powered by the same power plant as the
mux.
5.3. QRSS (Quasi Random Signal Sequence) TEST PATTERN
This pseudo-random sequence is based on a 20-bit shift register and generates every possible combination of 20-bits
(except all zero) and repeats every 1,048,756 bits. Before transmission into the network, this sequence is limited to 14
zeros so that it meets the 15-zero limitation when framed. The sequence has an average ones density of 50 percent.
This pattern is good for simulating traffic in a T1 system and has been shown to be similar in spectral content to voice
traffic.
Table 6: QRSS TEST PATTERN FOR AMI AND B8ZS LINE CODING
Pattern Average Ones Dens-
ity
Maximum Zeros Circuit Stressed
QRSS (un-framed) 50% 14 Timing and Equalization
QRSS (framed) 50% 15 Timing and Equalization
5.4. 1 in 8 PATTERN (also known as 1:7)
This pattern stresses the minimum ones density requirement for repeaters. This pattern will help determine if a timing
recovery problem exists with low-density patterns. When framed, the bits that are ones must be located in the second
bit position of each byte within the frame or a yellow alarm will occur. This test pattern is used to test the minimum ones
density for a B8ZS line code.
. . . 00 F 01000000 01000000 01000000 01. . .
AT&T Practice ATT-TP-000-000-006
Issue 1, 08/25/06
2006 AT&T Knowledge Ventures. All rights reserved
11